Tech Tools / Generator & Distro

Generator & Distro

Build a gear list, choose single-phase or 3-phase 120/208 V, see phase balance with suggestions, total kVA with 80% continuous derate, and a generator size class.

Use at your own risk. This is not an electrical design or a substitute for a licensed electrician. Wattages are typical planning figures. Confirm nameplates, connector ratings, cam-lok / feeder sizing, grounding, and local code before any show. Incorrect power can injure people and destroy gear.

Total watts
—
Total kW
—
1φ load current
—
Required gen (w/ 80%)
—
Suggested genset
—
Imbalance
—

—

—

Sources

  • Continuous loads: plan generator capacity so continuous load ≤ ~80% of rating.
  • kVA ≈ kW ÷ power factor. Default PF 0.8 for mixed show loads.
  • 3-phase auto-balance uses first-fit decreasing onto the lightest phase.
  • Cam-lok / feeder notes are reminders only — a licensed electrician must size and install.

What this generator planner does

It totals show wattage, optionally balances 3-phase legs, applies continuous-load derating, and suggests a generator kVA class.

Worked example

12 kW of mixed load at PF 0.8 → 15 kVA raw → ÷0.8 continuous ≈ 18.75 kVA → suggest a 25 kVA class genset with headroom.

FAQ

Why divide by 0.8?

Continuous loads are commonly planned at 80% of generator or breaker capacity.

Is auto phase balance perfect?

No. It greedily places loads on the lightest phase. Verify on site.

Can I use this instead of an electrician?

No. Hire a licensed electrician for design, tie-in, and safety.